M800V/M80V Series PLC Interface Manual
5 Appx.1: PLC window
5.2 PLC Window Interface
PLC -> NC interface signals
Signal name
PLC window Reading start R register n
PLC window Number of read windows n
PLC window Writing start R register n
PLC window Number of write windows n
 PLC window Reading start R register 1 to 3 (R424, R428, R432)
It sets the PLC window Reading start R register 1 to 3.
The setting range is 8300 to 9884, 18300 to 19884 and 28300 to 29884. (Even number only)
R register
R424
The value is not checked when the value of R425 is "0".
R428
The value is not checked when the value of R429 is "0".
R432
The value is not checked when the value of R433 is "0".
 PLC window Number of read windows 1 to 3 (R425, R429, R433)
It designates the number of read windows 1 to 3.
The setting range is 0 to 100. When it is 0, it does not read.
When a number from "1001" to "1100" is set, the number of windows of the extended interface is handled as "1" to "100".
R register
The read windows 1 will be the consecutive area for the number of windows designated.
R425
The read windows start from the R register designated with R424.
The read windows 2 will be the consecutive area for the number of windows designated.
R429
The read windows start from the R register designated with R428.
The read windows 3 will be the consecutive area for the number of windows designated.
R433
The read windows start from the R register designated with R432.
 PLC window Writing start R register 1 to 3 (R426, R430, R434)
It sets PLC window Writing start R register 1 to 3.
The setting range is 8300 to 9884, 18300 to 19884 and 28300 to 29884. (Even number only)
R register
R426
The value is not checked when the value of R427 is "0".
R430
The value is not checked when the value of R431 is "0".
R434
The value is not checked when the value of R435 is "0".
 PLC window Number of write windows 1 to 3 (R427, R431, R435)
It designates number of write windows 1 to 3.
The setting range is 0 to 100. When it is "0", it does not write.
When a number from "1001" to "1100" is set, the number of windows of the extended interface is handled as "1" to "100".
R register
The write windows 1 will be the consecutive area for the number of windows designated.
R427
The write windows start from the R register designated with R426.
The write windows 2 will be the consecutive area for the number of windows designated.
R431
The write windows start from the R register designated with R430.
The write windows 3 will be the consecutive area for the number of windows designated.
R435
The write windows start from the R register designated with R434.
R register (Common for part systems)
n=1
n=2
R424
R428
R425
R429
R426
R430
R427
R431
Details
Details
Details
Details
703
n=3
R432
R433
R434
R435
IB-1501616-D