MITSUBISHI ELECTRIC Mac E Series Human Machine Interface Installation Manual E1070 Art. no.: 169276 INDUSTRIAL AUTOMATION MITSUBISHI ELECTRIC 10 02 2006 Version A...
Page 3
Installation manual for the E1000 series operator terminals Foreword The E1000 operator terminal is developed to satisfy the demands of human- machine communication. Built-in functions such as displaying and controlling text, dynamic indication, time channels, alarm and recipe handling are included.
Safety Precautions Both the installer and the owner and/or operator of the operator terminal must read and understand this installation manual. 1.1 UL Installation Power, input and output (I/O) wiring must be in accordance with Class 1, Division 2 wiring methods (Article 501-4 (b) of the National Electric Code, NFPA 70) and in accordance with the authority having jurisdiction.
Safety Precautions 1.4 Service and Maintenance – Only qualified personnel should carry out repairs. – The agreed warranty applies. – Before carrying out any cleaning or maintenance operations, disconnect the equipment from the electrical supply. – Clean the display and surrounding front cover with a soft cloth and mild detergent.
Installation 2.1 Space Requirements – Installation plate thickness: 1.5 - 9.0 mm (0.06 - 0.35 inch) – Space requirements when installing the operator terminal: 177 mm (6.97 inch) 50 mm (2.0 inch) (11.22 inch) Caution The openings on the enclosure are for air convection. Do not cover these openings. 2.2 Installation Process 1.
Page 10
Installation 3. Secure the operator terminal in position, using all the fastening holes and the provided brackets and screws: 4. Connect the cables in the specified order. Caution Ensure that the operator terminal and the controller system have the same electrical grounding (reference voltage level), otherwise errors in communication may occur.
Installation 2.2.1 Mode Switches All mode switches must be in OFF position during operator terminal use. The mode switches should not be touched unless by qualified personell. 2.2.2 Connections to the Controller For information about the cables to be used when connecting the operator terminal to the controller, please refer to the help file for the driver in question.
Technical Data Parameter Front panel, W x H x D 285 x 177 x 6 mm Mounting depth 56 mm (156 mm including clearance) Front panel seal IP 66 Rear panel seal IP 20 Keyboard material Membrane switch keyboard with metal domes. Overlay film of Autotex F157 * with print on reverse side.
Page 14
Technical Data Mitsubishi Electric, MA00776...
Chemical Resistance 4.1 Metal Casing The frame and casing material is powder-coated aluminum. This powder paint withstands exposure of up to 24 hours duration to the following chemicals without visible change: Ammonia 25% De-ionized water Butanol Citric acid 10% Diesel Ethanol 99.5% denaturated FAM-Normal petrol Alcohol 95%...
Chemical Resistance Ammonia <40% Caustic soda <40% Hydrogen peroxide <25% Alkalicarbonate Bichromate Diesel oil Acetonitrile Sodium bisulphate Autotex withstands DIN 42 115 Part 2 exposure of up to 1 hour duration to glacial acetic acid without visible change. Autotex is not resistant to high pressure steam at over 100 C or the following chemicals: Concentrated mineral acids Concentrated caustic solution...