ABB RELION 670 Series Technical Manual page 279

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
7.7.3
Function block
I3P*
V3P*
BLOCK
DIRCND
ANSI08000430 V2 EN-US
Figure 132: FRPSPDIS (21) function block
7.7.4
Signals
Table 134: FRPSPDIS (21) Input signals
Name
I3P
V3P
BLOCK
DIRCND
Table 135: FRPSPDIS (21) Output signals
Name
TRIP
BFI
FWD_A
FWD_B
FWD_C
FWD_G
REV_A
REV_B
REV_C
Table continues on next page
Technical manual
FRPSPDIS (21)
TRIP
BFI
FWD_A
FWD_B
FWD_C
FWD_G
REV_A
REV_B
REV_C
REV_G
NDIR_A
NDIR_B
NDIR_C
NDIR_G
FWD_1PH
FWD_2PH
FWD_3PH
PHG_FLT
PHPH_FLT
PHSELZ
DLECND
ANSI08000430-2-en.vsd
Type
GROUP
SIGNAL
GROUP
SIGNAL
BOOLEAN
INTEGER
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Default
Description
-
Group signal for current input
-
Group signal for voltage input
0
Block of function
0
External directional condition
Description
Trip by pilot communication scheme logic
Start in any phase or loop
Fault detected in phaseA - forward direction
Fault detected in phase B - forward direction
Fault detected in phase C - forward direction
Ground fault detected in forward direction
Fault detected in phase A- reverse direction
Fault detected in phase B - reverse direction
Fault detected in phase C - reverse direction
Section 7
Impedance protection
GUID-4AE8EAC6-5231-4646-9215-33DBBA039B65 v2
PID-3643-INPUTSIGNALS v5
PID-3643-OUTPUTSIGNALS v5
273

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reg670

Table of Contents