ABB RELION 670 Series Technical Manual page 264

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 7
Impedance protection
Name
Values (Range)
IMinPUPP
10 - 1000
IMinPUPG
10 - 1000
IMinOpIR
5 - 1000
Table 128: ZMRPDIS (21) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 12
Table 129: ZMRAPDIS (21) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OperationDir
Non-directional
Forward
Reverse
X1PP
0.10 - 3000.00
R1PP
0.01 - 1000.00
X1PG
0.10 - 3000.00
R1PG
0.01 - 1000.00
RFPP
0.10 - 3000.00
X0PG
0.10 - 9000.00
RFPG
0.10 - 9000.00
R0PG
0.01 - 3000.00
OperationPP
Disabled
Enabled
OpModetPP
Disabled
Enabled
tPP
0.000 - 60.000
OperationPG
Disabled
Enabled
OpModetPG
Disabled
Enabled
tPG
0.000 - 60.000
IMinPUPP
10 - 1000
IMinPUPG
10 - 1000
258
Unit
Step
Default
%IB
1
20
%IB
1
20
%IB
1
5
Unit
Step
Default
-
1
1
Unit
Step
Default
-
-
Disabled
-
-
Forward
Ohm/p
0.01
30.00
Ohm/p
0.01
5.00
Ohm/p
0.01
30.00
Ohm/p
0.01
5.00
Ohm/l
0.01
30.00
Ohm/p
0.01
100.00
Ohm/l
0.01
100.00
Ohm/p
0.01
15.00
-
-
Enabled
-
-
Enabled
s
0.001
0.000
-
-
Enabled
-
-
Enabled
s
0.001
0.000
%IB
1
20
%IB
1
20
1MRK 502 066-UUS B
Description
Minimum operate delta current for Phase-
Phase loops
Minimum pickup phase current for Phase-
to-ground loops
Minimum operate residual current for
Phase-Ground loops
Description
Selection of one of the Global Base Value
groups
Description
Operation Disabled/Enabled
Operation mode of directionality NonDir /
Forw / Rev
Positive sequence reactance reach Ph-Ph
Positive seq. resistance for characteristic
angle, Ph-Ph
Positive sequence reactance reach Ph-G
Positive seq. resistance for characteristic
angle, Ph-G
Fault resistance reach in ohm/loop, Ph-Ph
Zero sequence reactance reach, Ph-G
Fault resistance reach in ohm/loop, Ph-G
Zero seq. resistance for zone
characteristic angle, Ph-G
Operation mode Disable/Enable of Phase-
Phase loops
Operation mode Disable/Enable of Zone
timer, Ph-Ph
Time delay of trip, Ph-Ph
Operation mode Disable/Enable of Phase-
Ground loops
Operation mode Disable/ Enable of Zone
timer, Ph-G
Time delay of trip, Ph-G
Minimum operate delta current for Phase-
Phase loops
Minimum pickup phase current for Phase-
to-ground loops
Technical manual
PID-3648-SETTINGS v5