ABB RELION 670 Series Technical Manual page 243

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
Table 110: ZDMRDIR (21D) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 12
Table 111: ZDARDIR Group settings (basic)
Name
Values (Range)
PolMode
-3U0
-V2
IPol
Dual
-3U0Comp
-V2comp
AngleRCA
-90 - 90
IPickup
5 - 200
VPolPU
4 - 100
IPolPU
5 - 100
Table 112: ZDARDIR Group settings (advanced)
Name
Values (Range)
AngleOp
90 - 180
Kmag
0.50 - 3000.00
Table 113: ZDARDIR Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 12
Technical manual
Unit
Step
Default
-
1
1
Unit
Step
Default
-
-
-3U0
Deg
1
75
%IB
1
5
%VB
1
4
%IB
1
10
Unit
Step
Default
Deg
1
160
Ohm
0.01
40.00
Unit
Step
Default
-
1
1
Impedance protection
Description
Selection of one of the Global Base Value
groups
Description
Polarization quantity for opt dir function
for P-G faults
Characteristic relay angle (= MTA or base
angle)
Minimum operation current in % of IBase
Minimum polarizing voltage in % of VBase
Minimum polarizing current in % of IBase
Description
Operation sector angle
Boost-factor in -V0comp and -V2comp
polarization
Description
Selection of one of the Global Base Value
groups
Section 7
PID-3564-SETTINGS v6
237