Edge [ii] Controller Operation Manual
SECTION 4: DIAGNOSTICS
4.6.3 onAER
The onAER screen displays several onAER communication parameters and provides the option
to perform two functionality and communication tests.
Main Menu → Diagnostics → Comm & Network →
1. Go to:
Figure 4.6.3: Comm & Network: onAer Screen
2. This screen displays the following read-only parameters:
Unit IP Address
•
Upload Time
•
Network Status
•
3. There are two optional tests of onAER functionality and communication. Both send reports
to the host server.
•
If you press the Test Heartbeat button, the green onAER LED on the Controller's front
face blinks rapidly for one or two seconds while sending a summary status file to the
host server.
•
If you press the Test Setup button, the green onAER LED on the Controller's front
face blinks rapidly for several seconds while sending a full status file to the host server.
Both buttons are greyed out until test completion.
•
OMM-139_E
8/25/2020
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
onAER.
Page 86 of 196