Edge [ii] Controller Operation Manual
SECTION 6 – ADVANCED SETUP
Purge Control
The Purge Control screen contains parameters associated with the purge process for this unit.
Main Menu → Advanced Setup → Performance → Fire Control → Purge
1. Go to:
2. This screen includes the following parameters:
Purge Blower Voltage: Allows adjustment of the blower speed (blower output
•
voltage) during the Purge cycle. (Range: 2.0 to 10.0 V)
Purge Timer: Allows adjustment of the pre-ignition purge time. (Range: 5 to 60 sec.)
•
Post Purge Timer: Allows adjustment of the purge time when a unit shuts down.
•
(Range: 0 to 60 sec.)
Ignition Control
The Ignition Control screen displays parameters related to ignition that apply to this unit only.
Main Menu → Advanced Setup → Performance → Fire Control → Ignition
1. Go to:
Control.
2. The following ignition control parameters are available:
•
OMM-139_E
8/25/2020
Figure 6.6.3.1: Fire Control: Purge Control
Figure 6.6.3.2: Fire Control: Ignition Control