Edge [ii] Controller Operation Manual
SECTION 7 – UNIT STATUS
The SmartPlate Status screen displays:
DHW Out: The SmartPlate's domestic hot water outlet temperature.
Valve Position: Boiler's valve position, percentage, setpoint and communication
address.
Status or error messages, shown below the screen title.

7.7 Runtime Statistics

The Runtime Statistics screen displays the unit's total run hours, total cycle count and a color-
coded honeycomb signifying the Average Cycles Per Hour.
STATUS = GREEN
The following notes apply to this screen:
The average cycles per run hour is calculated based on cycle count during rolling 1-
enabled-hour.
The Average Cycles Per Hour honeycomb is color coded are follows:
o Green = Less than 3 cycles per hour
o Yellow = Between 3 and 5 cycles per hour
o Red = More than 5 cycles per hour
If the cycle count exceeds 5 cycles per hour, an event is logged for a given unit (a high
cycle count does not lock out a unit).
OMM-139_E
8/25/2020
Figure 7.7: Runtime Statistics Screen
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
STATUS = RED
Page 178 of 196