Edge [ii] Controller Operation Manual
SECTION 6 – ADVANCED SETUP
2. Choose the Unit Application for this unit: DHW, Other or SH.
Unit Application = DHW
Figure 6.2.6-1: Unit Application Configuration
3. Depending on the Application chosen above, one of five Operating Modes appears.
Choose the Operating Mode appropriate for the unit:
TABLE 6.1: Operating Modes
Available Operating Modes
1 Constant Setpoint
2 Remote Setpoint
3 Direct Drive
4 Combination
5 Outdoor Reset
4. Depending on the Application and Operating Mode chosen in Steps 2 and 3, a number of
additional parameters appear. The table below shows which parameters appear for each
combination of Application and numbered Operating Mode.
TABLE 6.2: Unit Application Configuration Parameters
Available Parameters
1
Unit SH Operating Mode
2
Unit DHW Operating Mode
3
Unit Other Operating Mode
4
Unit SH Setpoint
5
Remote Signal
7
Unit Address
8
Unit Baud Rate
9
Unit DHW Setpoint
10 Analog Input Source 1
1
10 a Name
11 Unit DHW Remote Signal
OMM-139_E
8/25/2020
Application
SH
Unit Applications & Operating Modes (see table above)
1
2
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Unit Application = SH
DHW
Other
SH
3
4
5
1
DHW
Other
2
1
2
Page 103 of 196