Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
3. If you chose Remote Setpoint in step 1, the Select Remote Setpoint Type screen
appears. Choose how the unit will access the setpoint, then press Next.
Figure 2.3.2.1.1-4: BST Manager – Space Heating: Select Remote Setpoint Screen
A. If you chose 4-20mA, 0-20mA, 1-5V, or 0-5V, the SH Analog Input screen appears.
Enter the upper and lower limits of the SH setpoint in the BST SH Setpt
Low Limit and BST SH Setpt High Limit fields.
Pressing Next takes you to the Select BAS Mode screen; skip to
Completing the Installation
Figure 2.3.2.1.1-5: BST Manager – Space Heating: SH Analog Input Screen
B. If you chose either Network or BAS, the Select BAS Mode screen appears; skip to
Section 2.4: Completing the Installation
4. If you chose Outdoor Air Temperature Reset in Step 1, the Select Outdoor Reset Mode
screen appears. Choose the Outdoor Reset Mode and then press Next to continue.
Figure 2.3.2.1.1-6: BST Manager – Space Heating: Select Outdoor Reset Mode
OMM-139_E
8/25/2020
for instructions.
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
for instructions.
Section 2.4: