Edge [ii] Controller Operation Manual
SECTION 6 – ADVANCED SETUP
VSP Pump Speed Adjust: Use this parameter to adjust the voltage
signal to achieve the desired pump speed. For example, setting to 110% will
change the signal from 5.0V to 5.5V. (Range: 80 to 120%)
VSP Pump Off Delay: Specify the time delay after the unit stops firing
before shutting the pump off. (Range: 1 to 600 secs.)
VSP Pump Output: The voltage signal sent to the pump (read-only).
VSP Pump Relay: Displays if pump is On or Off
o The following parameters appear only if VSP Pump Mode = Fire Rate:
VSP Piping Configuration: Depending on the configuration of the plant,
choose either 1 Pump Per Blr or 1 Pump Per Plnt.
Boiler Plant Size: Specify how many boilers are in the plant.
(Range: 1 to 16)
Plant VSP Pump min spd: Specify the voltage that will drive the pump
at its minimum speed. (Range 0 to 10.0 V)
Plant VSP Pump max spd: Specify the voltage that will drive the pump
at its maximum speed. (Range 0 to 10.0 V)
Rem Blr VS Pump Add: Specify the address of the boiler to which the
variable speed pump is connected. (Range: 1 to 16)
o The following parameters appear only if VSP Pump Mode = Return Temp:
VSP Pump Decrease: Specify the amount the voltage signal will
increase/decrease for every VSP Pump Decr Time interval.
(Range: 0 to 100%)
VSP Pump Decr Time: Specify the interval at which the VSP Pump
Decrease signal is sent to the pump. (Range: 1 to 600 secs.)
VSP Pump Incr Time: Specify the amount of time for voltage signal to
the pump will reach full speed when Setpoint Limiting or High Temperature
occurs; this overrides VSP Pump Decrease and VSP Pump Decr Time.
When Setpoint Limiting or High Temperature condition ends, the VSP Pump
Decrease and VSP Pump Decr Time resumes. (Range: 1 to 600 secs.)

6.3.2 Cascade Communication

The Cascade Communication screen allows you to modify individual communication
parameters.
NOTES:
This screen is available only after BST functionality has been enabled (see the Unit Mode
parameter in
Section 6.3.1: Cascade
Manager, its parameters apply to this unit and all BST Client units.
Some parameters on this screen also appear in EZ Setup (see Section 2). While EZ Setup
is designed to walk you through the full configuring of a unit, this screen allows you modify
individual parameters, as needed.