Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
5. The next screen displays the current time and date. If both are correct, press Next to
continue. If not, press either field and enter the correct time or date and then press Save.
Figure 2.3.2-7: BST Manager: Date and Time Screen
6. Fill in the settings on the Cascade Communication screen, described below. When done,
press Next to continue.
Figure 2.3.2-4: BST Manager: Manager Communication Screen
NOTE:
Many of these parameters also appear in
individual settings can be easily changed at a later time.
Unit Address: The unique communication address of the current (Manager) unit.
(Range: 1 to 127)
Min & Max Address: The address range in the BST cascade, 1 up to the total
number of units in the cascade; for example, 1 and 10 (Max Address maximum = 16).
SSD Address: The Client/Client Device address. This parameter is for backwards
compatibility with the C-More Control system.
Cascade Baud Rate: Select the rate at which information is transferred in a
communication channel: 9600, 19200, 38400, 115200 bits per second.
Plant Failsafe Mode: The Manager's operating mode if there is a loss of
communication between the Manager and Client units, or to the BAS or external
signal/sensor, such as an outdoor sensor (default = Constant Setpoint).
Plant Failsafe Setpoint: (only if Plant Failsafe Mode = Constant Setpoint)
Specify the Setpoint for all units in the cascade.
OMM-139_E
8/25/2020
Section 6.3.2: Cascade
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Communication, where
Page 32 of 196