Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
Figure 2.3.2.1.3-5: BST Manager – Other: Other Analog Input Screen
B. If you chose Network, the Select BAS Mode screen appears. Skip to
Completing the Installation
EZ Setup: BST Manager – Two Applications
Complete the instructions in one of the three Sections below on the BST Manager if the unit
was configured to run two application. If it will run a single application, see Section 2.3.2.1.
2.3.2.2.1
EZ Setup: BST Manager – Space Heating and DHW Applications
Complete the instructions below only if you chose both Space Heating and DHW at the end of
Section 2.3.2.
Figure 2.3.2.2.1-1: BST Manager – SH & DHW: Select Your Boiler Application
1. When both Domestic Hot Water and Space Heating applications are chosen, Domestic
Hot Water priority mode is automatically activated and the DHW Priority screen appears (a
green border appears on the previous choice, if there was one). Set DHW Priority Mode
to one of the following then press Next to continue. (Note, your choice will affect which
options appear in Step 10, below.)
• 1 Swing Valve
OMM-139_E
8/25/2020
for instructions.
2 Swing Valves
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Section 2.4:
Setpoint Boost
Page 41 of 196