Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
Enter the upper and lower limits of the DHW setpoint in the DHW Setpt Low
Limit and DHW Setpt Hi Limit fields.
Pressing Next takes you to the Other Operating Mode screen (skip to Step 4).
Figure 2.3.2.2.2-5: BST Manager – DHW & Other: DHW Analog Input Screen
B. If you chose Network or BAS, the Other Operating Mode screen appears (see
Step 4).
4. When all DHW parameters have been configured, the Other Operating Mode screen
appears. Choose either Constant Setpoint or Remote Setpoint. Press Next to continue.
Figure 2.3.2.2.2-6: BST Manager – DHW & Other: Other Operating Mode Screen
5. If you chose Constant Setpoint, specify the setpoint for the "other" application. Pressing
Next takes you to the Select BAS Mode screen; skip to
Installation
for instructions.
Figure 2.3.2.2.2-7: BST Manager – DHW & Other: Other Heating Constant Setpoint
OMM-139_E
8/25/2020