Edge [ii] Controller Operation Manual
SECTION 7 – UNIT STATUS

7.1.3 Purging

1. All switches required to be met during the purge cycle (as shown above) have a checkbox,
which changes to green once the switch is met. If any switch fails to be proven, its
checkbox will turn red with a white X and the unit will display a fault message explaining the
failure. The safety circuit switches are:
Blower Proof
Purge Position
Blocked Inlet
Ignition Position
Figure 7.1.3: Ignition Sequence - Screen 3, Purge
2. The following additional parameters are displayed:
Purge Timer: The purge cycle's elapsed time in seconds
Valve Position Out: The Air Fuel Valve's position
Blower Voltage: The blower voltage as the unit purges
3. Upon expiration of purge timer, if all the switches are met, the Purging rectangle turns
green and the system progresses to Spark Cleaning. If the purge timer expires before all
the switches have been met, the Purging rectangle turns red.