Appendix A: Indoor/Outdoor Reset Ratio - Watts AERCO Edge [ii] Operation Manual

For benchmark boilers
Table of Contents

Advertisement

Edge [ii] Controller Operation Manual

Appendix A: Indoor/Outdoor Reset Ratio

Appendix A: Indoor/Outdoor Reset Ratio
Point 1:
OD Air Temp = 60˚
Min Water Temp = 100˚
Point 2:
OD Air Temp = -10˚
Max Water Temp = 185˚
High Limit:
HL (Water Temp) = 1950˚
Warm Weather Shutdown:
WWS = 70˚
OMM-139_E
8/25/2020
Outdoor Reset Ratio Set Point
Point 1
Descending Outdoor Temperature
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
High Limit
Example:
Outdoor = 30
Leads to Water SP = 136.4
Point 2
Page 193 of 196