Edge [ii] Controller Operation Manual
SECTION 6 – ADVANCED SETUP
4. For all values of Name except Not Assigned, configure the remaining parameters for the
input chosen in Step 2:
Min & Max Signal Level: Enter values in the Min and Max Signal Level parameters.
These two values define the range of the input signal. (Range: 0 to 100).
Min & Max Parameter Level: Enter values in the Min and Max Parameter Level
parameters. These two values define the range to which the analog input signal level
defined in Min & Max Signal Level will be linearly mapped. (Range: 0 to 100).
5. Configure the Rem Spr Ain # Addr (Remote Spare Analog In X Address, where X
corresponds to the input chosen in Step 2): Specify the address of the unit from which the
analog input signal is received. (Range: 0 to 16)
6. If needed, repeat Steps 2 – 5 for the other two analog inputs.

6.6 Performance

The Performance screen provides access to control and performance parameters for AERtrim,
Temperature and Fire Control functionality. All three Performance screens apply only to the
individual unit (they are not part of BST functionality).
Some unit level parameters are not applicable if BST is enabled. In that case, those parameters
are greyed out or hidden. As a result, the screens shown below may include parameters that
don't appear on the unit you are working on.
The AERtrim option is enabled only on units equipped with a functional O
is not detected or has faulted, the AERtrim button is greyed out.
Main Menu → Advanced Setup →
1. Go to:
NOTE:
You can navigate from one Performance screen to the next in round-robin fashion using the
Page Left and Page Right icons on each screen.
OMM-139_E
8/25/2020
Figure 6.6: Advanced Setting: Performance
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Performance.
sensor. If O
sensor
2
2
Page 155 of 196