Relays - Watts AERCO Edge [ii] Operation Manual

For benchmark boilers
Table of Contents

Advertisement

Edge [ii] Controller Operation Manual
SECTION 6 – ADVANCED SETUP
2. The following parameters Configure the Remote Interlock:
Remote Interlock Name: Choose one of the following:
o Flow
o Damper
Remote Intlk Use: Specifies what will shut down if the selected interlock switch is
open, either the individual boiler or the full system. Choose Sys Shutdown or Boiler
Shutdown.
3. The following parameters configure the Delayed Interlock. This interlock includes an
adjustable delay timer, which delays the ignition sequence, allowing sufficient time for a
proving switch to be made to prevent a fault.
Delayed Interlock Name: Choose one of the following:
o Valve 1
o Louver
Auxiliary Delay: Select the interlock delay. If the unit has a Sequencing Isolation
Valve, this must be set to 120 seconds (see
Installation Manual (
Valve). (Range: 0 to 240 sec.)

6.5.2 Relays

The Relays screen gives you the ability to configure up to two auxiliary relays: 'AUX 2' Relay
and 'PUMP 2' Relay.
Main Menu → Advanced Setup → Ancillary Device →
1.
Go to:
SELECT RELAY = V2/Spare 1 Relay
Figure 6.5.2: Ancillary Devices: Auxiliary Relays Screens
2. Press Select Relay and choose either V2/Spare 1 Relay or Spare 2 Relay.
3. In the Relay Name parameter, choose the name for the relay selected above:
V2/Spare 1 Relay Names
• Swing Valve 2
• Summer Pump
• Louver
• Damper
OMM-139_E
8/25/2020
o Louver
o Other
o Valve 2
o Louver 2
OMM-0136, GF-210) Section 2.14: BST Sequencing Isolation
System Pump
Pump 2
Louver 2
Sequenced Pump
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Benchmark PLATINUM-Edge:
Relays.
SELECT RELAY = Spare 2 Relay
Spare 2 Relay Names
System Pump
Pump 2
Louver 2
Sequenced Pump
Summer Pump
Louver
Damper
Other
Page 152 of 196

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents