Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
3. If you chose Remote Setpoint in Step 1, the Select Remote Setpoint Type screen
appears. Choose how the unit will access the setpoint, then press Next.
Figure 2.2.1-4: Standalone – Space Heating: Select Remote Setpoint Type Screen
A. If you chose 4-20mA, 0-20mA, 1-5V or 0-5V, the SH Analog Input screen appears.
Enter the upper and lower limits of the SH setpoint in the Unit SH Setpt Low
Limit and Unit SH Setpt High Limit fields. Pressing Next takes you to the
Select BAS Mode screen; skip to
instructions.
Figure 2.2.1-5: Standalone – Space Heating: SH Analog Input Screen
B. If you chose Network, the Comm Settings screen appears. Enter the Unit
Address and Unit Baud Rate. Pressing Next takes you to the Select BAS
Mode screen; skip to
Figure 2.2.1-6: Standalone – Space Heating: Comm Settings Screen
C. If you chose either BAS or PWM, the Select BAS Mode screen appears; skip to
Section 2.4: Completing the Installation
OMM-139_E
8/25/2020
Section 2.4: Completing the Installation
Section 2.4: Completing the Installation
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
for instructions.
for instructions.
for
Page 22 of 196