Edge [ii] Controller Operation Manual
SECTION 10 – STARTUP, STATUS, FAULT MESSAGES
TABLE 10-1: Edge Controller Fault Messages
#
FAULT MESSAGE
40
Remote Setpt Signal Fault
41
Outdoor Temp Sensor Fault
42
Outlet Temp Sensor Fault
43
FFWD Temp Sensor Fault
44
High Water Temp
45
Line Voltage Out of Phase
46
Stepper Motor Failure
47
Setpoint Limiting Active
48
Modbus Comm Fault
49
Wait Ignition Retry
50
WaitFault Purge
51
Wait Retry Pause
52
Exhaust Temp Sensor Short
53
Exhaust Temp Sensor Open
54
Warning Exhaust Temp High
55
Exhaust Temp High
56
Inlet Water Temp Sensor Short
57
Inlet Water Temp Sensor Open
58
Warning In Wtr Temp High
59
Warning In Wtr Temp Low
60
Inlet Gas Press Sensor Open
61
Gas Plate Dp Sensor Open
62
O2 Percentage Low
63
O2 Sensor Malfunction
64
Warning O2 Level High
65
Recirc Pump Failure
OMM-139_E
8/25/2020
DESCRIPTION
The Remote Setpoint signal is not present or is
out of range.
The temperature measured by the Outdoor Air
Sensor is out of range.
The temperature measured by the Outlet Sensor
is out of range:
OUTLET TEMPERATURE display = Sht
Indicates sensor is shorted
OUTLET TEMPERATURE display = Opn
indicates sensor is open-circuited
The temperature measured by the Feed Forward
(FFWD) Sensor is out of range.
The temperature measured by the Outlet Sensor
exceeded the Temp Hi Limit setting.
The Line (Hot) and Neutral wires are reversed.
The Stepper Motor failed to move the Air/Fuel
Valve to the desired position.
Outlet temperature crossed the high setpoint
limit. Setpoint limiting feature is active.
A network communication fault
The unit is waiting before retrying to ignite.
Fault while purging.
Pause before retrial for ignition.
The Exhaust Temp Sensor has malfunctioned.
Exhaust Temp Sensor is not connected or
malfunctioned.
The Exhaust temperature is above normal.
The Exhaust Temperature has exceeded 200°F
(93.3°C).
Inlet Water Temp Sensor has
malfunctioned/shorted out.
Inlet Water Temp Sensor is not connected or
malfunctioned.
Warning: Inlet water temperature is above
normal.
Warning: Inlet water temperature is below
normal.
Inlet Gas Pressure Sensor is not connected or
malfunctioned.
Gas Plate Dp Sensor is not connected or
malfunctioned.
The O2 % has gone below 2% for more than 30
seconds
Indicates O
than 24% for more than 10 seconds.
The O
is above normal operating limits.
2
The recirculation pump has failed.
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Levels are less than -4% or more
2
TYPE
Fault
Fault
Fault
Fault
Fault
Fault, Manual
Reset
Fault, Manual
Reset
Fault
Fault
Message
Message
Message
Warning
Warning
Warning
Fault, Manual
Reset
Warning
Warning
Warning
Warning
Fault
Fault
Fault
Fault
Warning
Fault, Manual
Reset
Page 189 of 196