Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
1. The SH Operating Mode screen appears. Choose the Operating Mode for the Space
Heating application, then press Next to continue:
Constant Setpoint
Remote Setpoint
Outdoor Air Temperature Reset (OATR)
Figure 2.3.2.1.1-2: BST Manager – Space Heating: SH Operating Mode Screen
NOTES:
If the outdoor air sensor is not connected, the display of the OAT (Outdoor Air
Temperature) at the bottom of the screen is disabled.
If the header sensor is not connected, the bottom of the screen displays HDR = --- °F. For
the header sensor to function without previous setup, the default for Outdoor Air Temp
Sens parameter must set to Direct (see
2. If you chose Constant Setpoint in step 1, specify the SH Setpoint. Pressing Next takes
you to the Select BAS Mode screen; skip to
instructions.
Figure 2.3.2.1.1-3: BST Manager – Space Heating: Constant Setpoint Screen