SECTION 6 – ADVANCED SETUP
DHCP Enabled
Figure 6.4.4: Comm & Network: Ethernet Screen
2. If DHCP is Disabled, manually enter the communication parameters, typically provided by a
network administrator, in the following parameters:
IP Address
Subnet
Gateway
DNS 1
DNS 2
3. If ICMP Ping is Enabled, the unit will respond to a ping from a network administrator.

6.4.5 Communication Failsafe

The Communication Failsafe option specifies how the unit will operate when either the
Manager communication or a Remote Signal is lost and the unit has to operate independently.
Main Menu → Advanced Setup → Comm & Network → Communication
1. Go to:
Figure 6.4.5: Comm & Network: Communication Failsafe Screen
2. Set the Failsafe Mode parameter to either Constant Setpoint or Shutdown.
If you chose Constant Setpoint, one additional parameter appears:
o Unit Failsafe Setpoint: Set it to the unit's default setpoint if
communication fails.
OMM-139_E
8/25/2020
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
DHCP Disabled
Failsafe.
Page 150 of 196