SECTION 6 – ADVANCED SETUP
6. If there are updated Graphics, I/O Board or Display files, the associated button(s) will be
colored red (update required) or yellow (update recommended). Press all red and yellow
buttons to initiate the update; if you press more than one button, the Controller automatically
starts the next update when the previous update completes. During each update, the
associated button is greyed out. Do not remove the USB device until the Update Finished
screen (Figure 6.2.7.4-1) appears.
7. To ensure the firmware update was successful, you must now turn the boiler's power OFF
and then back ON. Continue with the next step after restarting the boiler.
8. Once the Controller restarts, set the Enable/Disable switch back to Enable and remove the
USB device. If there was a problem with the update, see
9. Spot-check that the values recorded at the end of
should be performed whether or not the firmware update was successful.
a. Serial Number and Unit Type in
Settings.
b. Combustion Calibration Summary in
Summary.
c. Application Setup, in
abort.
10. If the spot-check is successful, the process is complete. But if any of the settings changed,
or you suspect the setup was corrupted, complete the instructions in the next section,
Section 6.2.7.5: Restore Settings After Firmware
OMM-139_E
8/25/2020
Figure 6.2.7.4-1: Update Finished Screen
Figure 6.2.7.4-2: Graphics Processing Screen
Main Menu → Advanced Setup → Unit → Unit
Main Menu → EZ
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Section 6.2.7.6:
Section 6.2.7.1
are still in effect. This step
Main Menu → Calibration → Combustion
Setup. See summary in first screen, then
Update.
Troubleshooting.