SECTION 3: CALIBRATION

3.4.2 Spark Monitor Calibration

The Spark Monitoring screen gives you the option of bounding the Spark Monitor's
measurement range by specifying the minimum and maximum spark current.
Figure 3.4.2: Subsystem: Spark Monitor Screen – Spark Monitor Enabled
Main Menu → Calibration → Subsystem → Spark
1. Go to:
2. To set a spark range, specify values in the following fields:
Min Spark: Range: 0.00 to 0.29 A
Max Spark: Range: 0.30 to 2.50 A

3.5 Combustion Summary

The Combustion Calibration Complete screen displays a summary of the results of the most
recent combustion calibration. It remains in effect until the next combustion calibration.
This screen also appears at the end of the Assisted Combustion Calibration (see Section 3.1:
Assisted Combustion Calibration) and Manual Combustion Calibration (see Section 3.2: Manual
Combustion Calibration).
Each cell is color coded with green or red honeycomb to indicate if each level is acceptable
Figure 3.5: Combustion Calibration Complete Screen
1. To view the summary, go to:
OMM-139_E
8/25/2020
Main Menu → Calibration → Combustion
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Monitoring.
Summary.