Edge [ii] Controller Operation Manual
SECTION 6 – ADVANCED SETUP

6.4.2 onAER

The onAER screen allows you to choose and configure how onAER will communicate with the
network.
Main Menu → Advanced Setup → Comm & Network →
1. Go to:
Figure 6.4.2: Comm & Network: onAER Screen
2. The onAER Mode parameter's default is Disabled. To enable onAER communication,
choose one of the following:
Ethernet: Requires an Ethernet cable to plugged into the Controller's left side, as
shown in Figure 6.2.7.1-1, in Section 6.2.7.1.
Wi-Fi: Requires the AERCO Wi-Fi module (P/N 24526-TAB) to be installed on the unit;
see the onAER Wi-Fi Module Installation Guide (TID-0178) for instructions.
Wiznet: This option intended for units on which the Edge Controller was installed as a
replacement for the C-More Controller.
3. Once enabled, the following additions parameters appear:
Unit Upload Time: This determines how frequently unit data will upload to the server,
in seconds. This will be split between unit data and cascade data (manager unit only).
(Range: 30 to 9999)
Cascade Upload Time: Determines how cascade data will upload to the server, in
seconds. (Range: 60 to 9999)
Status: Displays the communication interface status, which varies depending on the
interface selected in Step 2.
OMM-139_E
8/25/2020
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST