Edge [ii] Controller Operation Manual
SECTION 6 – ADVANCED SETUP
Node Offset: The starting address range for AERCO units.
•
Device Instance: Identifies the device on a BACnet network (read-only). It is
•
generated from the Node Offset added to the Communication Address field. This
value must be unique on a BACnet network.
Port Number: Specify the BAS port to which the unit will communicate.
•
(Range: 47808 to 47823)
Local IP Address: Displays the local IP address of the Edge Controller.
•
Status: Displays the status of BAS communications.
•
Security: Choose whether to Enable or Disable BAS Security. This option prohibits
•
communication to any devices as specified by the IP address and MAC address, per
parameters below. If enabled, the following additional parameters appear:
o BAS IP: Specifies the IP address of the BAS server.
o BAS MAC: Specifies the MAC address of the BAS server.
BAS Temp Format: Choose Fahrenheit, Celsius or Points.
•
Allow System Disable: If set to Yes (the default), a BAS front-end application can
•
initiate a system shutdown or an individual unit shutdown by writing 85 to one of the
addresses below via BACnet or Modbus (not available for ProtoNode). The BAS can
reenable the system/unit by sending 0 to the same address.
•
For BACnet
o BST Manager BACnet address 229
o BST Client BACnet address 80
•
For Modbus
o BST Manager Modbus address 40229
o BST Client Modbus address 40081
•