Summary of Contents for Watts Valpes VT PLUS Series
Page 2
Français ........................English ........................Instructions and security ......................Actuator description ..........................Dimensions ................................Electric wiring ..............................Recommendations ..................... Multipin connector ....................Electronic boards ............................Functioning modes ..........................Wired mode (permanent and pulse signal) ............... Positioning mode ....................... Bluetooth® mode (local control and weekly programming) ........Technical speci´cations ......................
Page 3
INSTRUCTIONS AND SECURITY DESCRIPTION These electric actuators have been designed to perform the control of a valve with 90° rotation. Please consult us for any different application. We cannot be held responsible if the mentioned actuators are used in contradiction to this advice.
Page 4
Control and power supply electronic board Aluminium cover + transparent Wheel porthole Position indicator Crankcase Detection switches F10/F12 & star 36 connection plate Motor + feedback Brushless motor Multipin connector '6%$ 5pYLVLRQ ...
Page 5
DIMENSIONS Square / Star Depth Diameter Depth ISO F connection M threaded Screws number (mm) (mm) (mm) (mm) ) ) ...
Page 6
Alternative Protection Direct current earth current As stipulated in the applicable regulation, the connection to earth contact is compulsory for devices with working voltages exceeding 42 V. The actuator is always powered, so it must be connected to a dis- connection system (switch, circuit breaker) to ensure the actuator power cut, correctly located, easily reached and marked as being the disconnecting device for the equipment.
Page 7
Seal Male connector 4 x CHC M6x30 inox A2 screws 4 x M3x10 screws 3 x ISO M20 x 1,5 cable glands Connector cover To wire the actuator, unscrew the 4 CHC M6x30 screws, and the 4 M3x10 screws. The wiring can be realized without tool, just raising the strips in front of each pin.
Page 8
ELECTRONIC BOARDS High voltage electronic board (SNBA050000) : 100V to 240V AC 50/60Hz and 100V to 300V DC Low voltage electronic board (SNBA051000) : 24V to 48V AC 50/60Hz and 24V to 72V DC 100V to 240V AC 50/60Hz and 100V to 300V DC 24V to 48V AC 50/60Hz and 24V to 72V DC TP/PE Feedback signal...
Page 9
FUNCTIONING MODE - Introduction Local control (Bluetooth ® ® Weekly scheduler (Bluetooth Wired (permanent & pulse signal) Positioning (learning mode) Positioning Keyboard local control (available soon) Mode selection Selection confirmation Description x Local control (Bluetooth®) : allows the use of the actuator from 20m maximum (in open field). This mode requires a smartphone or a tablet with the software.
Page 11
Validation led (pos.1) Validation led (pos. 2) Learning mode - closed position Learning mode - storage Learning mode - open position Feedback Set point signal signal Learning phase x Put the power on x With the « Next Mode » and « Ok Mode » buttons, select the learning mode (the APPR led is on) x Press «...
Page 12
FC1 feedback (NO) FC1 feedback common FC1 feedback (NC) FC2 feedback (NO) FC2 feedback common FC2 feedback (NC) Set point signal + Set point signal - Feedback + ( Feedback - Feedback + ( Neutral Phase AC 50/60Hz The 0-10V and 4- 20mA feedback signals are not available at the...
Page 13
Local control ® software allows the actuator control from 20m maximum (in open field). MART Weekly scheduling ® Thanks to software, the actuator can be programmed to schedule up to 20 tasks weekly repeatable. MART The actuator will become a stand-alone unit. For any further information, refer to the set up procedure (reference DSBA3302) '6%$ 5pYLVLRQ ...
Page 14
VT600 VT1000 installation Housing: Aluminium + EPOXY coating Materials Drive: Steel + Zn treatment Shafts and screws : Stainless steel IP68 Sealing Environment Both inside and outside (wet environments possible) -20°C to +70°C Operating temperature Operating altitude Altitude up to 2000m maximum relative humidity 80 % for temperatures up to 31 °C decreasing line- Hygrometry arly to 50 % relative humidity at 40 °C...
Page 15
Star 36 F10/F12 Star 46 F14 Star 46 F12/F16 Special Keyway bore Ø40 F12/F16 Standard Long operating time 100V to 240V 50Hz/ 60Hz and 100V to 300V DC 24V to 48V 50Hz / 60HZ and 24V to 72V DC 3-modulating points + ON-OFF mode 4-wire control 3-position Battery security system - normally closed...
Page 16
CR-TEC Engineering Inc. 15 Orchard Park Road, Unit 18 Madison, CT 06443-2268 info@crtec.com 203-318-9500...