Design Guidelines
Transport System Design
Ground
Proper grounding of the QuickStick HT transport system is required to make sure of proper
operation and to minimize electrical safety issues.
•
The bodies of the motors are grounded through the GND terminal on the motor.
•
The QSMC and QSMC-2 are grounded through the GND stud on the motor control-
lers.
•
The QSHT 5700 inverter is grounded through the GND stud on the inverter.
•
The NC LITE is not grounded through its power connection. The case of the NC LITE
must be grounded to an electrical safety ground (PE) through the mounting features.
•
The NC-12 is grounded through the GND stud on the node controller.
•
The NC-E and NC-S are grounded through the power connection.
•
All power supplies must be grounded to an electrical safety ground (PE) via the safety
ground in the AC input connector.
•
All junction boxes must be grounded to an electrical safety ground (PE).