5-10 Analog Monitor Output

The 3G3JV incorporates analog monitor output terminals AM and AC.
These terminals have analog monitor values of output frequency or cur-
rent.
Setting the Analog Monitor Output (n44 and n45)
The output frequency or current as a monitored item is set in n44.
The analog output characteristics are set as an analog monitor output gain in n45.
Analog Monitor Output
n44
Setting
0, 1
range
Set Values
Value
0
Output frequency (Reference: 10 V at max. frequency)
1
Output current (Reference: 10 V with rated output current)
n45
Analog Monitor Output Gain
Set range
0.00 to 2.00
Note 1. Set the multiplication ratio based on the set value in n44.
For example, if an output of 5 V is desired at maximum frequency (with n44 set
to 0), set n45 to 0.50.
Note 2. The maximum output voltage of the analog monitor output terminals are 10 V.
5-24