408 Parameters
No.
Name/Value
95.09
Switch fuse
controller
Disable
Enable
95.13
Reduced run mode
0...65535
95.14
Connected modules
Bit
Name
0
Module 1
1
Module 2
...
...
11
Module 12
12...15 Reserved
0000h...FFFFh
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
(Only visible with a BCU control unit)
Activates communication to a xSFC charging controller. This
setting is intended for use with inverter modules that are
connected to a DC bus through a DC switch/charging circuit
controlled by a charging controller. On units without a DC
switch, this parameter should be set to Disable.
The charging controller monitors the charging of the inverter
unit, and sends an enable command when the charging has
finished (ie. DC switch is closed after the 'charging OK' lamp
lights, and charging switch opened).
For more information, see xSFC documentation.
Communication with xSFC disabled.
Communication with xSFC enabled.
(Only visible with a BCU control unit)
Specifies the number of inverter modules available.
This parameter must be set if reduced run is required. A value
other than 0 activates the reduced run function.
If the control program cannot detect the number of modules
specified by this parameter, a fault
generated.
See section
Reduced run function
0 = Reduced run disabled
1...12 = Number of modules available
Number of inverter modules available
(Only visible with a BCU control unit)
Shows which of the parallel-connected inverter modules have
been detected by the control program.
Description
1 = Module 1 has been detected.
1 = Module 2 has been detected.
...
1 = Module 12 has been detected.
Inverter modules connected.
(5695 Reduced
run) is
(page 92).
Def/FbEq16
Enable
0
1
0
-
-
1 = 1