272 Parameters
No.
Name/Value
31.22
STO indication
run/stop
Fault/Fault
Fault/Warning
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Selects which indications are given when one or both Safe
torque off (STO) signals are switched off or lost. The
indications also depend on whether the drive is running or
stopped when this occurs.
The tables at each selection below show the indications
generated with that particular setting.
Notes:
• This parameter does not affect the operation of the STO
function itself. The STO function will operate regardless of
the setting of this parameter: a running drive will stop upon
removal of one or both STO signals, and will not start until
both STO signals are restored and all faults reset.
• The loss of only one STO signal always generates a fault
as it is interpreted as a malfunction.
For more information on the STO, see the Hardware manual
of the drive.
Inputs
Indication (running or stopped)
IN1
IN2
0
0
Fault
Faults
5091 Safe torque off
0
1
Faults
5091 Safe torque off
1
0
1
1
Inputs
IN1
IN2
Running
Fault
5091 Safe torque
0
0
off
Faults
5091 Safe
0
1
torque off
Safe torque off 1 loss
Faults
5091 Safe
1
0
torque off
Safe torque off 2 loss
1
1
5091 Safe torque off
and
FA81 Safe
torque off 1 loss
and
FA82 Safe
torque off 2 loss
(Normal operation)
Indication
Stopped
Warning
A5A0 Safe
torque off
Warning
A5A0 Safe
torque off
and fault
and
FA81
FA81 Safe torque off 1
loss
Warning
A5A0 Safe
torque off
and fault
and
FA82
FA82 Safe torque off 2
loss
(Normal operation)
Def/FbEq16
Fault/Fault
0
1