Advertisement

288 Parameters
No.
Name/Value
33.61
Value counter 2
warn limit
-2147483008 ...
2147483008
33.62
Value counter 2
function
Bit
Function
0
Counter mode
0 = Loop: When the limit is reached, the counter is reset. The counter status (bit 5 of
33.01) switches to 1 for one second. The warning (if enabled) stays active for at least 10
seconds.
1 = Saturate: When the limit is reached, the counter status (bit 5 of 33.01) switches to 1,
and remains so until
is reset.
1
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning (see 33.65) is given when the limit is reached
2...15
Reserved
0000b...0011b
33.63
Value counter 2
source
Not selected
Motor speed
Other
33.64
Value counter 2
divider
0.001 ...
2147483.000
33.65
Value counter 2
warn message
Value counter 2
exceeded
Maintain motor
bearing
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Sets the limit for value counter 2.
With a positive limit, bit 5 of
(and a warning optionally generated) when the counter is
equal or greater than the limit.
With a negative limit, bit 5 of
(and a warning optionally generated) when the counter is
equal or smaller than the limit.
0 = Counter disabled.
Limit for value counter 2.
Configures value counter 2.
33.60
is reset. The warning (if enabled) also stays active until
Value counter 2 configuration word.
Selects the signal to be monitored by value counter 2.
None (counter disabled).
01.01 Motor speed used
(see page 115).
Source selection (see
Terms and abbreviations
Defines a divisor for value counter 2. The value of the
monitored signal is divided by this value before integration.
Divisor for value counter 2.
Selects the optional warning message for value counter 2.
A88B Value counter
2. The message text can be edited on the
control panel by choosing Menu – Settings – Edit texts.
A880 Motor
bearing.
33.01 Counter status
is set to 1
33.01 Counter status
is set to 1
on page 112). -
Def/FbEq16
0
-
0000b
33.60
1 = 1
Not selected
0
1
1.000
-
Value
counter 2
exceeded
5
10