ABB ACS880 Firmware Manual page 411

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
95.20
HW options word 1
Bit
Name
0
Supply frequency
60 Hz
1
Emergency stop
Cat 0
2
Emergency stop
Cat 1
3
RO2 for -07
cabinet cooling fan
4
Externally powered
control unit
5
DC supply switch
6
DOL motor switch 1 = Motor fan control active. Affects 10.24, 35.100, 35.103, 35.104.
7
xSFC-01 fuse
switch controller
8
Service switch
9
Output contactor
10
Brake resistor, sine
filter, IP54 fan
11
INU-DSU
communication
12
Reserved
13
du/dt filter
activation
14
DOL fan activation 1 = The inverter unit consists of frame R8i modules with direct-on-
15
INU-ISU
communication
*See section
Control of a supply unit (LSU)
0000h...FFFFh
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Specifies hardware-related options that require differentiated
parameter defaults. Activating a bit in this parameter makes
the necessary changes in other parameters – for example,
activating an emergency stop option reserves a digital input.
In many cases, the differentiated parameters will also be
write-protected.
This parameter, as well as the changes in other parameters
implemented by it, are not affected by a parameter restore.
WARNING! After switching any bits in this word,
recheck the values of the affected parameters.
Information
0 = 50 Hz; 1 = 60 Hz. Affects parameters 11.45, 11.59, 12.20, 13.18,
30.11, 30.12, 30.13, 30.14, 31.26, 31.27, 40.15, 40.37, 41.15, 41.37,
46.01, 46.02.
1 = Emergency stop, Category 0, without FSO module. Affects
21.04, 21.05, 23.11.
1 = Emergency stop, Category 1, without FSO module. Affects
10.24, 21.04, 21.05, 23.11.
1 = Control of cabinet cooling fan (used only with specific
ACS880-07 hardware). Affects 10.27, 10.28, 10.29.
1 = Control unit powered externally. Affects 95.04. (Only visible with
a ZCU control unit)
1 = DC switch monitoring active. Affects 20.12, 31.03, 95.08. (Only
visible with a ZCU control unit)
1 = xSFC charging controller used. Affects 95.09. (Only visible with a
BCU control unit)
1 = Service switch connected. Affects 31.01, 31.02.
1 = Output contactor present. Affects 10.24, 20.12.
1 = Status (eg. thermal) switches connected to DIIL input. Affects
20.11, 20.12.
*1 = Diode supply unit control by inverter unit active. Makes several
parameters visible in groups 06, 60, 61,
a BCU control unit)
1 = Active: An external du/dt filter is connected to the drive output.
The setting will limit the output switching frequency. With inverter
module frame sizes R5i to R7i, the fan of the module will be forced to
full speed. Note: This bit is to be left at 0 if the drive/inverter module
is equipped with internal du/dt filtering (for example, frame R8i
inverter modules with option +E205).
line cooling fans (option +C188). Disables fan feedback monitoring
and changes fan control to ON/OFF type.
*1 = IGBT supply unit control by inverter unit active. Affects
and 95.02. Makes several parameters visible in groups 01, 05, 06,
07, 30, 31, 60, 61, 62,
(page 41).
Hardware options configuration word 1.
Parameters 411
62
and 94. (Only visible with
94
and 96.
Def/FbEq16
-
31.23
1 = 1