No.
Name/Value
01.106 Reactive current
0.00 ... 30000.00 A
01.108 Grid frequency
0.00 ... 100.00 Hz
01.109 Grid voltage
0.00 ... 2000.00 V
01.110
Grid apparent
power
-30000.00 ...
30000.00 kVA
01.112
Grid power
-30000.00 ...
30000.00 kW
01.114
Grid reactive power
-30000.00 ...
30000.00 kvar
01.116
LSU cos Φ
-1.00 ... 1.00
01.164 LSU nominal power
0...30000 kW
03

03 Input references

03.01
Panel reference
-100000.00 ...
100000.00
03.02
Panel reference 2
-30000.00 ...
30000.00
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
(Only visible when IGBT supply unit control activated by
95.20)
Estimated reactive current flowing through the supply unit.
Estimated reactive current.
(Only visible when IGBT supply unit control activated by
95.20)
Estimated frequency of the power supply network.
Estimated supply frequency.
(Only visible when IGBT supply unit control activated by
95.20)
Estimated voltage of the power supply network.
Estimated supply voltage.
(Only visible when IGBT supply unit control activated by
95.20)
Estimated apparent power being transferred through the
supply unit.
Estimated apparent power.
(Only visible when IGBT supply unit control activated by
95.20)
Estimated power being transferred through the supply unit.
Estimated supply power.
(Only visible when IGBT supply unit control activated by
95.20)
Estimated reactive power being transferred through the
supply unit.
Estimated reactive power.
(Only visible when IGBT supply unit control activated by
95.20)
Power factor of the supply unit.
Power factor.
(Only visible when IGBT supply unit control activated by
95.20)
Nominal power of the supply unit.
Nominal power.
Values of references received from various sources.
All parameters in this group are read-only unless otherwise
noted.
Local reference given from the control panel or PC tool.
Local control panel or PC tool reference.
Remote reference given from the control panel or PC tool.
Remote control panel or PC tool reference.
Parameters 119
Def/FbEq16
-
See par.
46.05
-
See par.
46.02
-
10 = 1 V
-
See par.
46.04
-
See par.
46.04
-
10 = 1 kvar
-
100 = 1
-
1 = 1 kW
-
1 = 10
-
1 = 10