Code
Fault
(hex)
64A3
Application loading
64A5
Licensing fault
64A6
Adaptive program
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Cause
Application file incompatible or
corrupted.
8006 Not enough memory for the
application.
8007 The application contains the
wrong system library version.
8008 The application is empty.
8009 The application contains
invalid tasks.
800A The application contains an
unknown target (system)
library function.
Running the control program is
prevented either because a
restrictive license exists, or
because a required license is
missing.
Error running the adaptive
program.
000A Program corrupted or block
non-existent
000C Required block input missing
000E Program corrupted or block
non-existent
0011 Program too large.
0012 Program is empty.
001C A nonexisting parameter or
block is used in the program.
001D Parameter type invalid for
selected pin.
001E Output to parameter failed
because the parameter was
write-protected.
0023 Program file incompatible with
current firmware version.
0024
002A Too many blocks.
Fault tracing 521
What to do
Check the auxiliary code. See actions for
each code below.
Reduce the size of the application.
Reduce the number of parameter
mappings.
See the drive-specific log generated by
Automation Builder.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
In Automation Builder, give a "Clean"
command and reload the application.
In Automation Builder, check application
task configuration, give a "Clean all"
command, and reload the application.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
Record the auxiliary codes of all active
licensing faults and contact your product
vendor for further instructions.
Check the auxiliary code (format
XXXX YYYY). "XXXX" specifies the
number of the function block (0000 =
generic error). "YYYY" indicates the
problem (see actions for each code
below).
Restore the template program or
download the program to the drive.
Check the inputs of the block.
Restore the template program or
download the program to the drive.
Remove blocks until the error stops.
Correct the program and download it to
the drive.
Edit the program to correct the parameter
reference, or to use an existing block.
Edit the program to correct the parameter
reference.
Check the parameter reference in the
program.
Check for other sources affecting the
target parameter.
Adapt the program to current block
library and firmware version.
Edit the program to reduce the number of
blocks.

Hide quick links: