ABB ACS880 Firmware Manual page 405

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
94.21
DC voltage ref
source
Zero
User ref
Other
94.22
User DC voltage
reference
0.0 ... 2000.0 V
94.30
Reactive power
reference
-3276.8 ... 3276.7
kvar
94.31
Reactive power ref
source
Zero
User ref
Other
94.32
User reactive power
reference
-3276.8 ... 3276.7
kvar
94.40
Power mot limit on
net loss
0.00 ... 600.00%
94.41
Power gen limit on
net loss
-600.00 ... 0.00%
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
(Only visible when IGBT supply unit control activated by
95.20)
Selects the source of the DC voltage reference to be sent to
the supply unit.
None.
94.22 User DC voltage
reference.
Source selection (see
Terms and abbreviations
(Only visible when IGBT supply unit control activated by
95.20)
Defines the DC voltage reference for the supply unit when
94.21 DC voltage ref source
User DC reference.
(Only visible when IGBT supply unit control activated by
95.20)
Displays the reactive power reference sent to the supply unit.
This parameter is read-only.
Reactive power reference sent to the supply unit.
(Only visible when IGBT supply unit control activated by
95.20)
Selects the source of the reactive power reference to be sent
to the supply unit.
None.
94.32 User reactive power
Source selection (see
Terms and abbreviations
(Only visible when IGBT supply unit control activated by
95.20)
Defines the reactive power reference for the supply unit when
94.31 Reactive power ref source
User reactive power reference.
Defines the maximum shaft power for motoring mode upon a
supply network failure when IGBT supply unit control is active
(bit 15 of
95.20 HW options word 1
The value is given in percent of nominal motor power.
Note: With a diode supply unit (bit 11 of
motoring shaft power is limited to 2% upon a network failure
regardless of this parameter.
Maximum shaft power for motoring mode upon a supply
network failure.
Defines the maximum shaft power for generating upon a
supply network failure when supply unit control is active (bit 11
or 15 of
95.20 HW options word 1
The value is given in percent of nominal motor power.
Maximum shaft power for generating mode upon a supply
network failure.
on page 112). -
is set to
User
ref.
reference.
on page 112). -
is set to
User
ref.
is on).
95.20
is on), the
is on).
Parameters 405
Def/FbEq16
User ref
0
1
0.0 V
10 = 1 V
-
10 = 1 kvar
User ref
0
1
0.0 kvar
10 = 1 kvar
600.00%
1 = 1%
-600.00%
1 = 1%