ABB ACS880 Firmware Manual page 82

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

82 Program features
FEN-xx encoder interfaces (optional) also have a connection for one KTY84 sensor.
The figure and table below show typical KTY84 sensor resistance values as a
function of the motor operating temperature.
KTY84 scaling
90 °C = 936 ohm
110 °C = 1063 ohm
130 °C = 1197 ohm
150 °C = 1340 ohm
The warning and fault limits can be adjusted by parameters.
For the wiring of the sensor, refer to the Hardware Manual of the drive.
Motor fan control logic (parameters 35.100...35.106)
If the motor has an external cooling fan, it is possible to use a drive signal (for
example, running/stopped) to control the starter of the fan via a relay or digital output.
A digital input can be selected for fan feedback. A loss of the feedback signal will
optionally cause a warning or a fault.
Start and stop delays can be defined for the fan. In addition, a feedback delay can be
set to define the time within which feedback must be received after the fan starts.
Ex motor support (parameter 95.15, bit 0)
The control program has a temperature protection function for Ex motors located in a
potentially explosive atmosphere. The protection is enabled by setting bit 0 of
parameter
95.15 Special HW
Settings
Parameter groups
35 Motor thermal protection
settings
(page 393); parameter
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Ohm
3000
2000
1000
0
-100
settings.
(page 289) and
95.15 Special HW settings
0
100
200
91 Encoder module
(page 409).
o
T
C
300

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents