158 Parameters
No.
Name/Value
Speed ref safe
12.04
AI supervision
selection
Bit
Name
0
AI1 < MIN
1
AI1 > MAX
2
AI2 < MIN
3
AI2 > MAX
4...15
Reserved
0000b...1111b
12.05
AI supervision force
Bit
Name
0
AI1 Ext1
1
AI1 Ext2
2
AI1 Local
3
Reserved
4
AI2 Ext1
5
AI2 Ext2
6
AI2 Local
7...15
Reserved
0000 0000b ...
0111 0111b
12.11
AI1 actual value
-22.000 ... 22.000
mA or V
12.12
AI1 scaled value
-32768.000 ...
32767.000
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Drive generates a warning
speed to the speed defined by parameter
safe
(or
28.41 Frequency ref safe
is being used).
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
Specifies the analog input limits to be supervised. See
parameter
12.03 AI supervision
Description
1 = Minimum limit supervision of AI1 active.
1 = Maximum limit supervision of AI1 active.
1 = Minimum limit supervision of AI2 active.
1 = Maximum limit supervision of AI2 active.
Activation of analog input supervision.
Activates analog input supervision separately for each control
location (see section
Local control vs. external control
page 20).
The parameter is primarily intended for analog input
supervision when the input is connected to the application
program and not selected as a control source by drive
parameters.
Description
1 = AI1 supervision active when EXT1 is being used.
1 = AI1 supervision active when EXT2 is being used.
1 = AI1 supervision active when local control is being used.
1 = AI2 supervision active when EXT1 is being used.
1 = AI2 supervision active when EXT2 is being used.
1 = AI2 supervision active when local control is being used.
Analog input supervision selection.
Displays the value of analog input AI1 in mA or V (depending
on whether the input is set to current or voltage by a hardware
setting).
This parameter is read-only.
Value of analog input AI1.
Displays the value of analog input AI1 after scaling. See
parameters
12.19 AI1 scaled at AI1 min
at AI1
max.
This parameter is read-only.
Scaled value of analog input AI1.
(A8A0 AI
supervision) and sets the
22.41 Speed ref
when frequency reference
function.
and
12.20 AI1 scaled
Def/FbEq16
4
0000b
1 = 1
0000 0000b
on
1 = 1
-
1000 = 1 mA
or V
-
1 = 1