ABB ACS880 Firmware Manual page 284

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

284 Parameters
No.
Name/Value
33.30
Edge counter 1
actual
0...4294967295
33.31
Edge counter 1
warn limit
0...4294967295
33.32
Edge counter 1
function
Bit
Function
0
Counter mode
0 = Loop: When the limit is reached, the counter is reset. The counter status (bit 2 of
33.01) switches to 1 and remains so until the counter is again incremented. The warning
(if enabled) stays active for at least 10 seconds.
1 = Saturate: When the limit is reached, the counter status (bit 2 of 33.01) switches to 1,
and remains so until
is reset.
1
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning (see 33.35) is given when the limit is reached
2
Count rising edges
0 = Disable: Rising edges are not counted
1 = Enable: Rising edges are counted
3
Count falling edges
0 = Disable: Falling edges are not counted
1 = Enable: Falling edges are counted
4...15
Reserved
0000b...1111b
33.33
Edge counter 1
source
False
True
RO1
Other [bit]
33.34
Edge counter 1
divider
1...4294967295
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Actual present value of signal edge counter 1.
The counter is incremented every time the signal selected by
parameter
33.33 Edge counter 1 source
either, depending on the setting of
function). A divisor may be applied to the count (see
Edge counter 1
divider).
When the counter exceeds the limit set by
1 warn
limit, bit 2 of
33.01 Counter status
warning specified by
33.35 Edge counter 1 warn message
also given if enabled by
33.32 Edge counter 1
The counter can be reset from the Drive composer PC tool, or
from the control panel by keeping Reset depressed for over 3
seconds.
Actual present value of signal edge counter 1.
Sets the warning limit for signal edge counter 1.
Warning limit for signal edge counter 1.
Configures signal edge counter 1.
33.30
is reset. The warning (if enabled) also stays active until
Edge counter 1 configuration word.
Selects the signal to be monitored by signal edge counter 1.
Constant 0.
Constant 1.
Bit 0 of
10.21 RO status
(page 149).
Source selection (see
Terms and abbreviations
Defines a divisor for signal edge counter 1. Determines how
many signal edges increment the counter by 1.
Divisor for signal edge counter 1.
switches on or off (or
33.32 Edge counter 1
33.34
33.31 Edge counter
is set to 1. The
is
function.
on page 112). -
Def/FbEq16
-
-
0
-
0000b
33.30
1 = 1
False
0
1
2
1
-