530 Fault tracing
Code
Fault
(hex)
FB14
Memory unit FW load
failed
FF61
ID run
0005...0008 Internal error.
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Cause
The memory unit is empty, or
contains incompatible or
corrupted firmware.
Motor ID run was not
completed successfully.
0001 Maximum current limit too low.
0002 Maximum speed limit or
calculated field weakening
point too low.
0003 Maximum torque limit too low.
0004 Current measurement
calibration did not finish within
reasonable time.
0009 (Asynchronous motors only)
Acceleration did not finish
within reasonable time.
000A (Asynchronous motors only)
Deceleration did not finish
within reasonable time.
What to do
Recycle the power to the control unit.
Check the sticker on the memory unit to
confirm that the firmware is compatible
with the control unit (ZCU-1x/BCU-x2).
Connect Drive composer PC tool
(version 2.3 or later) to the drive. Select
Tools - Recover drive.
If the problem persists, replace the
memory unit.
Check the nominal motor values in
parameter group
99 Motor
Check that no external control system is
connected to the drive.
Cycle the power to the drive (and its
control unit, if powered separately).
Check that the motor shaft is not locked.
Check the auxiliary code. The second
number of the code indicates the
problem (see actions for each code
below).
Check settings of parameters
Motor nominal current
and
Maximum
current. Make sure that
30.17
> 99.06.
Check that the drive is dimensioned
correctly according to the motor.
Check settings of parameters
•
30.11 Minimum speed
•
30.12 Maximum speed
•
99.07 Motor nominal voltage
•
99.08 Motor nominal frequency
•
99.09 Motor nominal
speed.
Make sure that
•
30.12
> (0.55 × 99.09) >
(0.50 × synchronous speed)
•
30.11
< 0, and
• supply voltage > (0.66 × 99.07).
Check settings of parameter
nominal
torque, and the torque limits in
group
30
Limits.
Make sure that the maximum torque limit
in force is greater than 100%.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
data.
99.06
30.17
99.12 Motor