40.14
Set 1 setpoint
scaling
-32768.00 ...
32767.00
40.15
Set 1 output scaling
-32768.00 ...
32767.00
40.16
Set 1 setpoint 1
source
Not selected
Control panel
Internal setpoint
AI1 scaled
AI2 scaled
Motor
potentiometer
Freq in scaled
Setpoint data
storage
Other
40.17
Set 1 setpoint 2
source
40.18
Set 1 setpoint
function
In1 or In2
In1+In2
In1-In2
In1*In2
In1/In2
MIN(In1,In2)
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Defines, together with parameter
general scaling factor for the process PID control chain.
The scaling can be utilized when, for example, the process
setpoint is input in Hz, and the output of the PID controller is
used as an rpm value in speed control. In this case, this
parameter might be set to 50, and parameter
nominal motor speed at 50 Hz.
In effect, the output of the PID controller = [40.15] when
deviation (setpoint - feedback) = [40.14] and [40.32] = 1.
Note: The scaling is based on the ratio between
40.15. For example, the values 50 and 1500 would produce
the same scaling as 1 and 30.
Process setpoint base.
See parameter
40.14 Set 1 setpoint
Process PID controller output base.
Selects the first source of process PID setpoint. This setpoint
is available in parameter
40.25 Set 1 setpoint selection
setpoint 1. See the control chain diagram on page 590.
None.
03.01 Panel reference
(see page 119). See section
control panel as an external control source
Internal setpoint. See parameter
sel1.
12.12 AI1 scaled value
(see page 158).
12.22 AI2 scaled value
(see page 160).
22.80 Motor potentiometer ref act
potentiometer).
11.39 Freq in 1 scaled
(see page 154).
40.92 Setpoint data storage
Source selection (see
Terms and abbreviations
Selects the second source of process setpoint. This setpoint
is available in parameter
40.25 Set 1 setpoint selection
setpoint 2.
For the selections, see parameter
source.
Selects a mathematical function between the setpoint sources
selected by parameters
40.16 Set 1 setpoint 1 source
40.17 Set 1 setpoint 2
source.
No mathematical function applied. The source selected by
parameter
40.25 Set 1 setpoint selection
Sum of sources 1 and 2.
Source 2 subtracted from source 1.
Source 1 multiplied by source 2.
Source 1 divided by source 2.
Smaller of the two sources.
40.15 Set 1 output
scaling, a
40.15
to the
40.14
scaling.
Using the
(page 21).
40.19 Set 1 internal setpoint
(output of the motor
(see page 319).
on page 112). -
40.16 Set 1 setpoint 1
and
is used.
Parameters 309
Def/FbEq16
100.00
and
1 = 1
1500.00;
1800.00
(95.20
b0)
1 = 1
Internal
as
setpoint
0
1
2
3
4
8
10
24
Not selected
as
In1 or In2
0
1
2
3
4
5