Modbus Holding Register Addresses - ABB ACS880 Firmware Manual

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Fieldbus control through the embedded fieldbus interface (EFB) 553

Modbus holding register addresses

The table below shows the default Modbus holding register addresses for drive data.
This profile provides a converted 16-bit access to the data.
Register address
400001
400002
400003
400004
400005
400006
400007...400024
400025
400089
...
400090
400100
...
400101
465536
...
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Register data (16-bit words)
Control word. See section
The selection can be changed using parameter
Reference 1 (REF1).
The selection can be changed using parameter
Reference 2 (REF2).
The selection can be changed using parameter
Status Word (SW). See section
The selection can be changed using parameter
Actual value 1 (ACT1).
The selection can be changed using parameter
Actual value 2 (ACT2).
The selection can be changed using parameter
Data in/out 7...24.
Selected by parameters
Unused
Error code access. See section
400090...400100)
(page 560).
Parameter read/write.
Parameters are mapped to register addresses according to parameter
58.33 Addressing
mode.
Control Word
(page 547).
Status Word
(page 549).
58.107 Data I/O 7
...
58.124 Data I/O
Error code registers (holding registers
58.101 Data I/O
1.
58.102 Data I/O
2.
58.103 Data I/O
3.
58.104 Data I/O
4.
58.105 Data I/O
5.
58.106 Data I/O
6.
24.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents