ABB ACS880 Firmware Manual page 318

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

318 Parameters
No.
Name/Value
40.54
Set 1 trim mix
0.000 ... 1.000
40.55
Set 1 trim adjust
-100.000 ...
100.000
40.56
Set 1 trim source
PID ref
PID output
40.57
PID set1/set2
selection
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
Other [bit]
40.60
Set 1 PID activation
source
Off
On
Follow Ext1/Ext2
selection
DI1
DI2
DI3
DI4
DI5
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
When parameter
40.51 Set 1 trim mode
defines the effect of direct and proportional trim sources in the
final trimming factor.
0.000 = 100% proportional
0.500 = 50% proportional, 50% direct
1.000 = 100% direct
Trim mix.
Defines a multiplier for the trimming factor. This value is
multiplied by the result of parameter
Consequently, the result of the multiplication is used to
multiply the result of parameter
Multiplier for trimming factor.
Selects the reference to be trimmed.
PID setpoint.
PID controller output.
Selects the source that determines whether process PID
parameter set 1 (parameters 40.07...40.56) or set 2 (group
Process PID set
2) is used.
0 = Process PID parameter set 1 in use
1 = Process PID parameter set 2 in use
0.
1.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Digital input/output DIO1
(11.02 DIO delayed
Digital input/output DIO2
(11.02 DIO delayed
Source selection (see
Terms and abbreviations
Selects a source that enables/disables process PID control.
See also parameter
40.07 Set 1 PID operation
0 = Process PID control disabled.
1 = Process PID control enabled.
0.
1.
Process PID control is disabled when external control location
EXT1 is active, and enabled when external control location
EXT2 is active.
See also parameter
19.11 Ext1/Ext2
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
is set to Combined,
40.51 Set 1 trim
mode.
40.56 Set 1 trim
source.
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
status, bit 0).
status, bit 1).
on page 112). -
mode.
selection.
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
Def/FbEq16
0.000
1 = 1
1.000
1 = 1
PID ref
1
2
Not selected
41
0
1
2
3
4
5
6
7
10
11
On
0
1
2
3
4
5
6
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents