436 Parameters
No.
Name/Value
99.18
Sine filter
inductance
0.000 ...
100000.000 mH
99.19
Sine filter
capacitance
0.00 ... 100000.00
µF
200

200 Safety

This group contains parameters related to the optional FSO-xx safety functions module. For details, refer to
the documentation of the FSO-xx module.
206
207
208
209
206 I/O bus
configuration
207 I/O bus service
208 I/O bus diagnostics
209 I/O bus fan
identification
These groups contain parameters related to the distributed I/O bus, which is used with some drives for
monitoring the cooling fans of the cabinet system. For details, refer to ACS880 distributed I/O bus supplement
(3AXD50000126880 [English]).
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Defines the inductance of a custom sine filter, ie. when
parameter
95.15 Special HW settings
Note: For an ABB sine filter
this parameter is set automatically and should not be
adjusted.
Inductance of custom sine filter.
Defines the capacitance of a custom sine filter, ie. when
parameter
95.15 Special HW settings
If the capacitors are star/wye-connected, enter the
capacitance of one leg into the parameter.
Drive
Sine filter
If the capacitors are delta-connected, multiply the capacitance
of one leg by 3 and enter the result into the parameter.
Drive
Sine filter
Note: For an ABB sine filter
this parameter is set automatically and should not be
adjusted.
Capacitance of custom sine filter.
FSO-xx settings.
Distributed I/O bus settings.
These groups are only visible with a BCU control unit.
bit 3 is activated.
(95.15 Special HW settings
bit 3 is activated.
C
C
C
99.19
C
C
99.19
C
(95.15 Special HW settings
Def/FbEq16
-
bit 1),
1000 = 1 mH
-
M
3~
= C
M
3~
= 3 × C
bit 1),
100 = 1 µF