ABB ACS880 Firmware Manual page 293

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
1 × Pt100 analog
I/O
2 × Pt100 analog
I/O
3 × Pt100 analog
I/O
PTC DI6
PTC analog I/O
PTC encoder
module 1
PTC encoder
module 2
Direct temperature
1 × Pt1000 analog
I/O
2 × Pt1000 analog
I/O
3 × Pt1000 analog
I/O
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Pt100 sensor connected to a standard analog input selected
by parameter
35.24 Temperature 2 AI source
output. The input and output can be on the drive control unit or
on an extension module.
The required settings are the same as with selection
analog
I/O, except that the source selection parameter of the
analog output must be set to
As selection
1 × Pt100 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
As selection
1 × Pt100 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
PTC sensor connected to digital input DI6 (see the connection
diagram on page 80).
Note: Either 0 ohm (normal temperature) or 4000 ohm
(excessive temperature) will be shown by
temperature
2. By default, an excessive temperature will
generate a warning as per parameter
warning
limit. If you want a fault instead, set
Temperature 2 fault limit
to 4000 ohm.
PTC sensor connected to a standard analog input selected by
parameter
35.24 Temperature 2 AI source
output. The input and output can be on the drive control unit or
on an extension module.
The required settings are the same as with selection
analog
I/O, except that the source selection parameter of the
analog output must be set to
PTC sensor connected to encoder interface 1.
See also parameters
91.21 Module 1 temp sensor type
91.22 Module 1 temp filter
PTC sensor connected to encoder interface 2.
See also parameters
91.24 Module 2 temp sensor type
91.25 Module 2 temp filter
The temperature is taken from the source selected by
parameter
35.24 Temperature 2 AI
source is assumed to be in the unit of temperature specified
by
96.16 Unit
selection.
Pt1000 sensor connected to a standard analog input selected
by parameter
35.24 Temperature 2 AI source
output. The input and output can be on the drive control unit or
on an extension module.
The required settings are the same as with selection
analog
I/O, except that the source selection parameter of the
analog output must be set to
As selection
1 × Pt1000 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
As selection
1 × Pt1000 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
and an analog
Force Pt100
excitation.
I/O, but with two sensors
I/O, but with three sensors
35.03 Measured
35.23 Temperature 2
35.22
and an analog
Force PTC
excitation.
time.
time.
source. The value of the
and an analog
Force Pt1000
excitation.
I/O, but with two sensors
I/O, but with three sensors
Parameters 293
Def/FbEq16
5
KTY84
6
7
8
20
KTY84
9
and
10
and
11
13
KTY84
14
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents