Fieldbus control through the embedded fieldbus interface (EFB) 551

References

The ABB drives profile supports the use of two references, EFB reference 1 and EFB
reference 2. The references are 16-bit words each containing a sign bit and a 15-bit
integer. A negative reference is formed by calculating the two's complement from the
corresponding positive reference.
The references are scaled as defined by parameters 46.01...46.07; which scaling is
in use depends on the setting of
page 355).
Fieldbus
The scaled references are shown by parameters
EFB reference
2.
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
58.26 EFB ref1 type
46.01
(with speed reference)
20000
46.02
(with frequency reference)
46.03
(with torque reference)
10000
46.04
(with power reference)
0 (with torque or power reference)
0
±(46.06) (with speed reference)
±(46.07) (with frequency reference)
-(46.03) (with torque reference)
-10000
-(46.04) (with power reference)
-(46.01) (with speed reference)
-20000
-(46.02) (with frequency reference)
and
58.27 EFB ref2 type
Drive
03.09 EFB reference 1
(see
and
03.10