ABB ACS880 Firmware Manual page 409

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
95.15
Special HW
settings
Bit
Name
0
EX motor
1
ABB sine filter
2
High speed mode
3
Custom sine filter
4...15
Reserved
0000b...0111b
95.16
Router mode
Off
On
Other [bit]
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Contains hardware-related settings that can be enabled and
disabled by toggling the specific bits.
Note: The installation of the hardware specified by this
parameter may require derating of drive output, or impose
other limitations. Refer to the hardware manual of the drive.
Information
1 = The driven motor is an Ex motor provided by ABB for potentially
explosive atmospheres. This sets the required minimum switching
frequency for ABB Ex motors. Note: For non-ABB Ex motors,
contact your local ABB representative.
1 = An ABB sine filter is connected to the output of the drive/inverter.
1 = Minimum switching frequency limit adaptation to output
frequency active. This setting improves control performance at high
output frequencies (typically above 120 Hz).
1 = A custom sine filter is connected to the output of the
drive/inverter. See also parameters 97.01, 97.02, 99.18, 99.19.
Hardware options configuration word.
(Only visible with a BCU control unit)
Enables/disables router mode of the BCU control unit. When
router mode is active, the PSL2 channels connected to
another BCU (ie. those selected by
config) are routed to the power units (inverter modules)
connected to this BCU.
See section
Router mode for BCU control unit
Router mode inactive.
Router mode active.
Source selection (see
Terms and abbreviations
Parameters 409
95.17 Router channel
(page 94).
on page 112). -
Def/FbEq16
-
1 = 1
Off