No.
Name/Value
40.04
Process PID
deviation actual
-32768.00 ...
32767.00
40.05
Process PID trim
output act
-32768.00 ...
32767.00
40.06
Process PID status
word
Bit
Name
0
PID active
1
Setpoint frozen
2
Output frozen
3
PID sleep mode
4
Sleep boost
5
Trim mode
6
Tracking mode
7
Output limit high
8
Output limit low
9
Deadband active
10
PID set
11
Reserved
12
Internal setpoint
active
13...15 Reserved
0000h...FFFFh
40.07
Set 1 PID operation
mode
Off
On
On when drive
running
40.08
Set 1 feedback 1
source
Not selected
AI1 scaled
AI2 scaled
Freq in scaled
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Displays the process PID deviation. By default, this value
equals setpoint - feedback, but deviation can be inverted by
parameter
40.31 Set 1 deviation
chain diagram on page 591.
This parameter is read-only. The unit is selected by parameter
40.12 Set 1 unit
selection.
PID deviation.
Displays the trimmed reference output. See the control chain
diagram on page 591.
This parameter is read-only. The unit is selected by parameter
40.12 Set 1 unit
selection.
Trimmed reference.
Displays status information on process PID control.
This parameter is read-only.
Value
1 = Process PID control active.
1 = Process PID setpoint frozen.
1 = Process PID controller output frozen.
1 = Sleep mode active.
1 = Sleep boost active.
1 = Trim function active.
1 = Tracking function active.
1 = PID output is being limited by par. 40.37.
1 = PID output is being limited by par. 40.36.
1 = Deadband active (see par. 40.39)
0 = Parameter set 1 in use. 1 = Parameter set 2 in use.
1 = Internal setpoint active (see par. 40.16...40.24)
Process PID control status word.
Activates/deactivates process PID control. See also
parameter
40.60 Set 1 PID activation
Note: Process PID control is only available in external control;
see section
Local control vs. external control
Process PID control inactive.
Process PID control active.
Process PID control is active when the drive is running.
Selects the first source of process feedback. See the control
chain diagram on page 590.
None.
12.12 AI1 scaled value
(see page 158).
12.22 AI2 scaled value
(see page 160).
11.39 Freq in 1 scaled
(see page 154).
Parameters 307
inversion. See the control
source.
(page 20).
Def/FbEq16
-
1 = 1 unit
-
1 = 1 unit
-
1 = 1
Off
0
1
2
AI1 scaled
0
1
2
3