536 Fault tracing
Code
Fault / Aux. code
(hex)
5E05
Rating ID mismatch
5E06
Main contactor Fault
6E19
Synchronization fault
6E1A
Rating ID fault
6E1F
Licensing fault
7E01
Panel loss
8E07
Net lost
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Cause
The hardware of the supply
unit does not match the
information stored in the
memory unit. This may occur
eg, after a firmware update or
memory unit replacement.
Control program does not
receive main contactor on (1)
acknowledgement through
digital input even control
program has closed the
contactor control circuit with
relay output.
Main contactor / main breaker
is not functioning properly, or
there is a loose / bad
connection.
Synchronization to supply
network has failed.
Rating ID load error.
There are two types of licenses
being used in ACS880 drives:
licenses that need to be found
from the unit which allow the
firmware to be executed, and
licenses that prevent the
firmware from running.The
license is indicated by the
value of the auxiliary code
field. The license is Nxxxx,
where xxxx is indicated by the
4-digit value of the auxiliary
code field.
8201 A restrictive license is found
from the unit. The firmware on
this supply unit cannot be
executed because a Low
harmonic license is found from
the unit. This unit is meant to
be used with IGBT supply
control program (2Q) only.
Control panel or PC tool
selected as active control
location has ceased
communicating.
Net lost is detected. Duration
of net lost is too long.
What to do
Cycle the power to the supply unit. If the
control unit is externally powered, reboot
the control unit (using parameter
LSU control board
boot) or by cycling its
power.
If the problem persists, contact your local
ABB representative.
Check main contactor / main breaker
control circuit wiring.
Check the status of other switches
connected to contactor control circuit.
See the delivery-specific circuit
diagrams.
Check main contactor operating voltage
level (should be 230 V).
Check digital input DI3 connections.
Monitor possible network transients.
Contact your local ABB representative.
Check the line-converter control
program. Record the auxiliary codes of
all active licensing faults and contact your
product vendor for further instructions.
This fault requires a reboot of the control
unit either by switching the power off and
on, or using parameter
96.108 LSU
control board
boot.
Contact your product vendor for further
instructions.
Check PC tool or control panel
connection.
Check control panel connector.
Replace control panel in mounting
platform.
Resynchronize the IGBT supply unit to
the grid after net lost.
96.108