ABB ACS880 Firmware Manual page 519

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Code
Fault
(hex)
5690
PU communication
internal
5691
Measurement circuit
ADC
5692
PU board powerfail
5693
Measurement circuit
DFF
5694
PU communication
configuration
5695
Reduced run
5696
PU state feedback
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Cause
Internal communication error.
Measurement circuit fault.
Power unit power supply
failure.
Measurement circuit fault.
Number of connected power
modules differs from expected.
Number of inverter modules
detected does not match the
value of parameter
95.13
Reduced run
mode.
State feedback from output
phases does not match control
signals.
Fault tracing 519
What to do
Contact your local ABB representative.
If the control unit is externally powered,
check the setting of parameter
Control board
supply.
If the problem persists, contact your local
ABB representative, quoting the auxiliary
code.
Check the auxiliary code (format
ZZZY YYXX). "YY Y" specifies the
affected inverter module (0...C, always 0
for ZCU control units). "XX" specifies the
affected power supply (1: Power supply
1, 2: Power supply 2, 3: both supplies).
Contact your local ABB representative,
quoting the auxiliary code.
Check setting of
95.31 Parallel type
configuration. Cycle the power to the
drive. If the control unit is externally
powered, also reboot the control unit
(using parameter
96.08 Control board
boot) or by cycling its power.
If the problem persists, contact your local
ABB representative.
Check that the value of
95.13 Reduced
run mode
corresponds to the number of
inverter modules present. Check that the
modules present are powered from the
DC bus and connected by fiber optic
cables to the BCU control unit.
If all modules of the inverter unit are in
fact available (eg. maintenance work has
been completed), check that parameter
95.13
is set to 0 (reduced run function
disabled).
Contact your local ABB representative,
quoting the auxiliary code.
95.04